2 of 230three-phase rack PDUs close 1× GB300 NVL72 (142 kW) · NEC 125% rule
- Server Technology — 415 V / 80 A — ×1.30
- Server Technology — 400 V / 125 A — ×1.95
Loading the catalog…
| Server Technology | PRO4X Switched POPS PDU | 400 | 125 | 86.6 | ● ×1.95 | ↗ | |
| ▸ | Server Technology | PRO4X Switched POPS PDU | 415 | 80 | 57.6 | ● ×1.30 | ↗ |
| Eaton | Managed HDX PDU G4 ×6 identical | 208 | 100 | 36.0 | — ×0.81 | ↗ | |
| Tripp Lite | 3-Phase Managed HDX Rack PDU G4, 240/415V, 36 Outlets (27 C13 + | 220 | 60 | 34.6 | — ×0.78 | ↗ | |
| Tripp Lite | 3-Phase Managed HDX Rack PDU G4, 240/415V, 39 Outlets (27 C13 + | 220 | 60 | 34.6 | — ×0.78 | ↗ | |
| Tripp Lite | 3-Phase Managed HDX Rack PDU G4, 240/415V, 42 Outlets (36 C13 + | 220 | 60 | 34.6 | — ×0.78 | ↗ | |
| Tripp Lite | 3-Phase Managed HDX Rack PDU G4, 240/415V, 45 C13 Outlets, 60A, | 220 | 60 | 34.6 | — ×0.78 | ↗ | |
| Tripp Lite | 3-Phase Managed HDX Rack PDU G4, 240/415V, 48 Outlets (42 C13 + | 415 | 60 | 34.6 | — ×0.78 | ↗ | |
| Tripp Lite | 3-Phase Managed HDX Rack PDU G4, 240/415V, 51 C13 Outlets, 60A, | 220 | 60 | 34.6 | — ×0.78 | ↗ | |
| APC | NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 43.5kW 400V | 415 | 48 | 34.5 | — ×0.78 | ↗ | |
| APC | NetShelter Rack PDU Advanced Gen 2, Switched Metered Outlet, 3Ph | 415 | 48 | 34.5 | — ×0.78 | ↗ | |
| APC | NetShelter Rack PDU Advanced Gen 2, Switched, 34.6kW, 3Phase, 43 | 415 | 48 | 34.5 | — ×0.78 | ↗ | |
| APC | NetShelter Rack PDU Advanced, Metered, 3Phase, 43.5kW 400V 63A o | 415 | 48 | 34.5 | — ×0.78 | ↗ | |
| APC | NetShelter Rack PDU Advanced, Switched Metered Outlet, 3Phase, 4 | 415 | 48 | 34.5 | — ×0.78 | ↗ | |
| APC | NetShelter Rack PDU Advanced, Switched, 3Phase, 43.5kW 400V 63A | 415 | 48 | 34.5 | — ×0.78 | ↗ | |
| Eaton | Managed HDX PDU G4 ×5 identical | 208 | 80 | 28.8 | — ×0.65 | ↗ | |
| Eaton | Switched PDU PDU3XVSR6G63B (3-Phase Vertical, 3Φ In, 1Φ Out) | 400 | 40 | 27.7 | — ×0.62 | ↗ | |
| Eaton | Switched PDU PDU3XVSRHWA (3-Phase Vertical, 3Φ In, 1Φ Out) | 400 | 40 | 27.7 | — ×0.62 | ↗ | |
| Eaton | Switched PDU PDU3XVSRHWB (3-Phase Vertical, 3Φ In, 1Φ Out) | 400 | 40 | 27.7 | — ×0.62 | ↗ | |
| Tripp Lite | PDU3XVSR6G63B 3-Phase Vertical Switched PDU (3φ In, 1φ Out) | 400 | 40 | 27.7 | — ×0.62 | ↗ | |
| Eaton | Managed HDX PDU G4 ×5 identical | 240 | 64 | 26.6 | — ×0.60 | ↗ | |
| Eaton | 3-Phase Switched 0U PDU (380-415V) ×2 identical | 380 | 40 | 26.3 | — ×0.59 | ↗ | |
| Eaton | Switched PDU PDU3XVSR6G63A (3-Phase Vertical, 3Φ In, 1Φ Out) | 380 | 40 | 26.3 | — ×0.59 | ↗ | |
| Tripp Lite | PDU3XVSR6G60A 3-Phase Vertical Switched PDU (3φ In, 1φ Out) | 415 | 35 | 25.2 | — ×0.57 | ↗ | |
| Tripp Lite | PDU3XVSR6G60B 3-Phase Vertical Switched PDU (3φ In, 1φ Out) | 415 | 35 | 25.2 | — ×0.57 | ↗ | |
| CyberPower | PDU33110 | MONITORED PDU SERIES | 240 | 60 | 24.9 | — ×0.56 | ↗ | |
| CyberPower | PDU83108 SWITCHED METERED-BY-OUTLET PDU | 240 | 60 | 24.9 | — ×0.56 | ↗ | |
| Eaton | Managed HDX PDU G4 ×14 identical | 240 | 60 | 24.9 | — ×0.56 | ↗ | |
| Eaton | Metered Outlet HDX PDU G4 | 240 | 60 | 24.9 | — ×0.56 | ↗ | |
| Eaton | 3-Phase Switched 0U PDU (380-415V) ×2 identical | 380 | 35 | 23.0 | — ×0.52 | ↗ | |
| Server Technology | PRO4X Smart POPS PDU ×2 identical | 415 | 32 | 23.0 | — ×0.52 | ↗ | |
| Server Technology | PRO4X Switched POPS PDU | 415 | 32 | 23.0 | — ×0.52 | ↗ | |
| Server Technology | PRO4X Switched PDU | 415 | 32 | 23.0 | — ×0.52 | ↗ | |
| Server Technology | PRO4X Switched PDU C4W48RA-U6BD2FD3 | 415 | 32 | 23.0 | — ×0.52 | ↗ | |
| Eaton | G3 Universal Input Rack PDU (G3 UPDU) | 208 | 63 | 22.7 | — ×0.51 | ↗ | |
| APC | NetShelter Metered Rack PDU, 2G, 0U, 23.0kW, 240V, 30 C13 and 12 | 400 | 32 | 22.2 | — ×0.50 | ↗ | |
| APC | Rack PDU, Basic, 1U, 22kW, 400V, (13) C13 Outlets | 400 | 32 | 22.2 | — ×0.50 | ↗ | |
| Eaton | Switched PDU PDU3XVSR6G32B (3-Phase Vertical, 3Φ In, 1Φ Out) | 400 | 32 | 22.2 | — ×0.50 | ↗ | |
| Tripp Lite | PDU3XVSR6G32B 3-Phase Vertical Switched PDU (3φ In, 1φ Out) | 400 | 32 | 22.2 | — ×0.50 | ↗ | |
| Server Technology | PRO4X Smart PDU | 220 | 32 | 22.0 | — ×0.50 | ↗ | |
| Eaton | Managed HDX PDU G4 ×5 identical | 208 | 60 | 21.6 | — ×0.49 | ↗ | |
| Eaton | 3-Phase Switched 0U PDU (380-415V) ×2 identical | 380 | 32 | 21.1 | — ×0.47 | ↗ | |
| Eaton | Switched PDU PDU3XVSR6G32A (3-Phase Vertical, 3Φ In, 1Φ Out) | 380 | 32 | 21.1 | — ×0.47 | ↗ | |
| CyberPower | PDU13104 | BASIC PDU SERIES | 240 | 50 | 20.8 | — ×0.47 | ↗ | |
| CyberPower | PDU33108 | MONITORED PDU SERIES | 240 | 50 | 20.8 | — ×0.47 | ↗ | |
| CyberPower | PDU83107 Switched Metered-by-Outlet PDU | 240 | 50 | 20.8 | — ×0.47 | ↗ | |
| Eaton | EMIU03-06 ePDU G3 Metered Input | 240 | 48 | 20.0 | — ×0.45 | ↗ | |
| Eaton | ePDU G3 Metered Outlet Rack PDU EMO330-06 | 240 | 48 | 20.0 | — ×0.45 | ↗ | |
| Eaton | horizontal rack PDU G4 - Managed PDU G4 (EHMA5606Q) | 240 | 48 | 20.0 | — ×0.45 | ↗ | |
| Eaton | horizontal rack PDU G4 - Metered-input PDU G4 (EHMI5606Q) | 240 | 48 | 20.0 | — ×0.45 | ↗ | |
| Eaton | ePDU G3 Metered Input | 240 | 48 | 20.0 | — ×0.45 | ↗ | |
| Eaton | ePDU G3 Metered Input (EMU29-06) | 240 | 48 | 20.0 | — ×0.45 | ↗ | |
| Eaton | Universal Input Rack PDU CordSet - Pigtails (3P Delta 208V) | 208 | 55 | 19.8 | — ×0.45 | ↗ | |
| Eaton | Managed Rack PDU G4 (Remote management with outlet-level monitor ×2 identical | 346 | 32 | 19.2 | — ×0.43 | ↗ | |
| Eaton | Metered Input Rack PDU G4 (Remote management with bank-level mon | 346 | 32 | 19.2 | — ×0.43 | ↗ | |
| Eaton | ePDU G3 Metered Input | 240 | 45 | 18.7 | — ×0.42 | ↗ | |
| APC | Rack PDU, Switched, Zero U, 12.5kW, 208V, (21)C13 & (3)C19, 10' | 208 | 50 | 18.0 | — ×0.41 | ↗ | |
| Eaton | Power Controller (Engineering Drawing PC3038-3074, ASSY 3074) | 208 | 50 | 18.0 | — ×0.41 | ↗ | |
| Raritan | PXE-1772V | 208 | 50 | 18.0 | — ×0.41 | ↗ | |
| Eaton | ePDU G3 Basic | 200 | 48 | 17.3 | — ×0.39 | ↗ | |
| Server Technology | PRO4X Smart PDU | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| Server Technology | PRO4X Smart POPS PDU ×3 identical | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| Server Technology | PRO4X Smart PDU C4S36RA-DQBD2FE1 | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| Server Technology | PRO4X Switched PDU ×2 identical | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| Tripp Lite | 3-Phase Managed Rack PDU G4, 208V, 42 Outlets, 48A, 17.3kW, 460P | 208 | 60 | 17.3 | — ×0.39 | ↗ | |
| Tripp Lite | 3-Phase Metered Input Rack PDU G4, 208V, 42 Outlets, 48A, 17.3kW ×2 identical | 208 | 60 | 17.3 | — ×0.39 | ↗ | |
| APC | NetShelter Metered Rack PDU, 0U, 17.3kW, 208V, 3 phase, 60A, 30 | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| APC | NetShelter Metered Rack PDU, 2G, 0U, 17.2kW, 208V, 6 C13 and 12 | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| APC | NetShelter Rack PDU Advanced Gen 2, Metered Outlet, 3Phase, 17.3 | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| APC | NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 17.3kW, 208 | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| APC | NetShelter Rack PDU Advanced Gen 2, Switched Metered Outlet, 3Ph | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| APC | NetShelter Rack PDU Advanced Gen 2, Switched, 3Phase, 17.3kW, 20 | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| APC | NetShelter Rack PDU Advanced, Metered Outlet, 3Phase, 17.3kW, 20 | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| APC | NetShelter Rack PDU Advanced, Metered, 3Phase, 17.3kW, 208V 60A, | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| APC | NetShelter Rack PDU Advanced, Switched Metered Outlet, 3Phase, 1 | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| APC | NetShelter Rack PDU Advanced, Switched, 3Phase, 17.3kW, 208V 60A | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| APC | NetShelter Rack PDU, Metered, 0U, 17.3kW 208V 3-phase 60A, (6) C | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| APC | NetShelter Switched Rack PDU, 9K series, 0U, 17.3kW, 208V, 20 C1 | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| APC | NetShelter Switched Rack PDU, 9K series, 0U, 17.3kW, 208V, 42 C1 | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| APC | Rack PDU 2G, Switched, 17.2kW, 208V, (20) C13, (12)C19 (BEING DI | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| APC | Rack PDU 2G, ZeroU, 17.2kW, 208V, (42) C13, (6) C19 (BEING DISCO | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| Eaton | UPDU G4 input cable - 460P9W 10 ft. (CBL356-10) | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| Eaton | UPDU G4 input cable - 460P9W 6 ft. (CBL356-06) | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| Eaton | Universal Input Rack PDU CordSet - IEC 60309 460P9W, IP67 | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| Eaton | Universal Input Rack PDU CordSet - IEC 60309 560P9W, IP67 | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| Tripp Lite | PDU360AT6G60 3-Phase Horizontal Monitored ATS PDU (3φ In, 1φ Out | 208 | 48 | 17.3 | — ×0.39 | ↗ | |
| Tripp Lite | 3-Phase Managed HDX Rack PDU G4, 208V, 24 C39 Outlets, 60A, 17kW | 200 | 60 | 17.3 | — ×0.39 | ↗ | |
| Tripp Lite | 3-Phase Managed HDX Rack PDU G4, 208V, 36 Outlets (24 C13 + 12 C | 200 | 60 | 17.3 | — ×0.39 | ↗ | |
| Tripp Lite | 3-Phase Managed HDX Rack PDU G4, 208V, 48 C13 Outlets, 60A, 17kW | 200 | 60 | 17.3 | — ×0.39 | ↗ | |
| Tripp Lite | 3-Phase Managed HDX Rack PDU G4, 208V, 48 Outlets (24 C13 + 24 C | 200 | 60 | 17.3 | — ×0.39 | ↗ | |
| Tripp Lite | 3-Phase Managed HDX Rack PDU G4, 208V, 54 Outlets (42 C13 + 12 C | 200 | 60 | 17.3 | — ×0.39 | ↗ | |
| Eaton | EMIU04-06 G3 Metered Input ePDU | 240 | 40 | 16.6 | — ×0.37 | ↗ | |
| Eaton | ePDU G3 Metered Outlet Rack PDU | 240 | 40 | 16.6 | — ×0.37 | ↗ | |
| Eaton | Managed Rack PDU G4 (Remote management with outlet-level monitor ×2 identical | 200 | 48 | 16.6 | — ×0.37 | ↗ | |
| Eaton | Metered Input Rack PDU G4 (Remote management with bank-level mon ×2 identical | 200 | 48 | 16.6 | — ×0.37 | ↗ | |
| APC | Rack PDU, Metered, Zero U, 16.2KW, 208V, (12)C19 & (3)C13 | 208 | 45 | 16.2 | — ×0.37 | ↗ | |
| APC | Rack PDU, Metered, Zero U, 16.2KW, 208V, (12)C19 & (3)C13 6FT Co | 208 | 45 | 16.2 | — ×0.37 | ↗ | |
| Eaton | 3-Phase Switched 0U PDU (208V) | 208 | 45 | 16.2 | — ×0.37 | ↗ | |
| Tripp Lite | PDU3VN6G60C 3-Phase Vertical Monitored PDU (3φ In, 1φ Out) | 208 | 45 | 16.2 | — ×0.37 | ↗ | |
| Tripp Lite | PDU3VSR6G60A 3-Phase Vertical Switched PDU (3φ In, 1φ Out) | 208 | 45 | 16.2 | — ×0.37 | ↗ | |
| Eaton | 3-Phase Monitored 0U PDU (200-240V) | 200 | 45 | 15.6 | — ×0.35 | ↗ | |
| Eaton | EBAU28-10 G3 BASIC ePDU | 240 | 35 | 14.5 | — ×0.33 | ↗ | |
| APC | NetShelter Basic Rack PDU, 1U, 14.4kW, 208V, 6 C19 outlet | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| APC | NetShelter Basic Rack PDU, Zero U, 14.4kW, 208V, 24 C13, 4 C19, ×2 identical | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| APC | NetShelter Metered Rack PDU, 0U, 14.4kW, 208V, 24 C13, 4 C19, 2 | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| APC | NetShelter Metered Rack PDU, Zero U, 14.4kW, 208V, 24 C13, 4 C19 | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| APC | NetShelter Rack PDU Advanced Gen 2, Metered, 3Phase, 14.4kW, 208 | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| APC | NetShelter Rack PDU Advanced Gen 2, Switched Metered Outlet, 3Ph | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| APC | NetShelter Rack PDU Advanced Gen 2, Switched, 3Phase, 14.4kW, 20 | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| APC | NetShelter Rack PDU Advanced, Metered, 3Phase, 14.4kW, 208V 50A, | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| APC | NetShelter Rack PDU Advanced, Switched Metered Outlet, 3Phase, 1 | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| APC | NetShelter Rack PDU Advanced, Switched, 3Phase, 14.4kW, 208V 50A | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| APC | Rack PDU, Basic, 1U, 14.4kW, (13) C13 Outlets | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| APC | Rack PDU, Basic, Zero U, 14.4kW, 208 V, (6) C19 & (3) C13, High | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| APC | Rack PDU, Metered, Zero U, 14.4kW, 208V, (24)C13, (4)C19, (2)L6- | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| APC | Rack PDU, Metered, Zero U, 14.4kW, 208V, (6) C19 | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| APC | Rack PDU, Metered, Zero U, 14.4kW, 208V, (6) C19, High Temp | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| APC | Rack PDU,Metered,ZeroU, 14.4kW,208V,(24)C13,(4)C19, (2)L6-30R, 3 | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| Eaton | UPDU G4 input cable - CS8365 10 ft. (CBL364-10) | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| Eaton | UPDU G4 input cable - CS8365 6 ft. (CBL364-06) | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| Eaton | ePDU G3 Metered Input | 240 | 40 | 14.4 | — ×0.32 | ↗ | |
| Server Technology | PRO4X Switched PDU | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| Server Technology | PRO4X Smart PDU | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| Server Technology | PRO4X Smart POPS PDU | 208 | 40 | 14.4 | — ×0.32 | ↗ | |
| Eaton | Managed Rack PDU G4 (Remote management with outlet-level monitor | 200 | 40 | 13.9 | — ×0.31 | ↗ | |
| Eaton | Metered Input Rack PDU G4 (Remote management with bank-level mon | 200 | 40 | 13.9 | — ×0.31 | ↗ | |
| Eaton | Universal Input Rack PDU CordSet - IEC 60309 560P6W, IP67 | 240 | 32 | 13.3 | — ×0.30 | ↗ | |
| Eaton | Universal Input Rack PDU CordSet - Pigtails (3P Wye 240/415V) | 240 | 32 | 13.3 | — ×0.30 | ↗ | |
| Bachmann | BlueNet BN ESSENTIAL Metered PDU | 230 | 32 | 12.7 | — ×0.29 | ↗ | |
| Eaton | Universal Input Rack PDU CordSet - IEC 60309 532P6, IP44 | 230 | 32 | 12.7 | — ×0.29 | ↗ | |
| APC | NetShelter Basic Rack PDU, Zero U, 12.5kW, 208V, 30 C13 and 6 C1 ×2 identical | 208 | 35 | 12.6 | — ×0.28 | ↗ | |
| APC | NetShelter Metered Rack PDU, 2G, 0U, 10.0kW, 208V, 36 C13 and 6 | 208 | 35 | 12.6 | — ×0.28 | ↗ | |
| APC | NetShelter Rack PDU, Metered, 0U, 10kW 208V 3-phase 50A, (36) C1 | 208 | 35 | 12.6 | — ×0.28 | ↗ | |
| APC | NetShelter Switched Rack PDU, Zero U, 12.5KW, 208V, 21 C13 and 3 | 208 | 35 | 12.6 | — ×0.28 | ↗ | |
| APC | NetShelter Switched Rack PDU, Zero U, 12.5kW, 208V, 21 C13 and 3 | 208 | 35 | 12.6 | — ×0.28 | ↗ | |
| APC | Rack PDU, Metered, Zero U, 12.5kW, 208V, (30)C13, (6)C19; 10' Co | 208 | 35 | 12.6 | — ×0.28 | ↗ | |
| APC | Rack PDU, Metered, Zero U, 12.5kW, 208V, (30)C13, (6)C19; 3' Cor | 208 | 35 | 12.6 | — ×0.28 | ↗ | |
| APC | Rack PDU, Switched, Zero U, 12.5kW,208V,(21)C13&(3)C19,3' Cord | 208 | 35 | 12.6 | — ×0.28 | ↗ | |
| Tripp Lite | PDU3VN10G60 3-Phase Vertical Monitored PDU (3φ In, 1φ Out) | 208 | 35 | 12.6 | — ×0.28 | ↗ | |
| Tripp Lite | PDU3VN10G60BW 3-Phase Vertical Monitored PDU (3φ In, 1φ Out) | 208 | 35 | 12.6 | — ×0.28 | ↗ | |
| Tripp Lite | PDU3VN3G60 3-Phase Vertical Monitored PDU (3φ In, 1φ Out) | 208 | 35 | 12.6 | — ×0.28 | ↗ | |
| Tripp Lite | PDU3VN6G60B 3-Phase Vertical Monitored PDU (3φ In, 1φ Out) | 208 | 35 | 12.6 | — ×0.28 | ↗ | |
| Tripp Lite | PDU3VS6H50 3-Phase Vertical Switched PDU (3φ In, 1φ Out) | 208 | 35 | 12.6 | — ×0.28 | ↗ | |
| Tripp Lite | PDU3VSR10G60 3-Phase Vertical Switched PDU (3φ In, 1φ Out) | 208 | 35 | 12.6 | — ×0.28 | ↗ | |
| Eaton | ePDU G3 Managed | 200 | 35 | 12.5 | — ×0.28 | ↗ | |
| CyberPower | PDU83104 Switched Metered-by-Outlet PDU | 240 | 30 | 12.5 | — ×0.28 | ↗ | |
| CyberPower | PDU83105 Switched Metered-by-Outlet PDU | 240 | 30 | 12.5 | — ×0.28 | ↗ | |
| CyberPower | PDU83106 Switched Metered-by-Outlet PDU | 240 | 30 | 12.5 | — ×0.28 | ↗ | |
| Eaton | 3-Phase Monitored 0U PDU (200-240V) ×3 identical | 200 | 35 | 12.1 | — ×0.27 | ↗ | |
| Eaton | 3-Phase Switched 0U PDU (200-240V) | 200 | 35 | 12.1 | — ×0.27 | ↗ | |
| Eaton | EMIU02-10 G3 Metered Input | 200 | 35 | 12.1 | — ×0.27 | ↗ | |
| CyberPower | PDU33105 | Monitored PDU Series | 208 | 30 | 10.8 | — ×0.24 | ↗ | |
| Eaton | 3-Phase Metered Rackmount PDU ×2 identical | 208 | 30 | 10.8 | — ×0.24 | ↗ | |
| Eaton | 3-Phase Monitored 0U PDU (208V) | 208 | 30 | 10.8 | — ×0.24 | ↗ | |
| Eaton | High Density (HD) Rack PDU line (from "Quick guide to power dist | 208 | 30 | 10.8 | — ×0.24 | ↗ | |
| Raritan | PXE-1955V | 208 | 30 | 10.8 | — ×0.24 | ↗ | |
| Tripp Lite | 3-Phase Metered Rackmount PDU ×2 identical | 208 | 30 | 10.8 | — ×0.24 | ↗ | |
| Tripp Lite | 3-Phase Monitored Rack-Mount PDU | 208 | 30 | 10.8 | — ×0.24 | ↗ | |
| Tripp Lite | 3-Phase Switched Rack-Mount PDU | 208 | 30 | 10.8 | — ×0.24 | ↗ | |
| Tripp Lite | PDU330AT6L1530 3-Phase Horizontal Monitored ATS PDU (3φ In, 1φ O | 208 | 30 | 10.8 | — ×0.24 | ↗ | |
| Eaton | 3-Phase Switched 0U Vertical PDU | 200 | 30 | 10.4 | — ×0.23 | ↗ | |
| Tripp Lite | 3-Phase Monitored 0U Vertical PDU ×4 identical | 200 | 30 | 10.4 | — ×0.23 | ↗ | |
| Eaton | PC3037 (ASSY 3037) Rack Mounted Power Distribution Unit | 120 | 30 | 6.2 | — ×0.14 | ↗ | |
| Eaton | rack PDU G4e Managed PDU EMA333-10 | 120 | 30 | 6.2 | — ×0.14 | ↗ | |
| Eaton | rack PDU G4e Metered-input PDU EMI310-10 | 120 | 30 | 6.2 | — ×0.14 | ↗ | |
| Eaton | TPC4100-C (ASSY 4102) 3-Phase Rack Mount Power Distribution Unit | 120 | 30 | 6.2 | — ×0.14 | ↗ | |
| Eaton | Three-Phase Power Controller (Pulizzi Z-Line), Assy 2481 | 120 | 30 | 6.2 | — ×0.14 | ↗ | |
| Eaton | Basic Rack PDU G4 (Reliable, cost-effective power distribution w | 415 | 63 | n/p | ? phase? | ↗ | |
| Eaton | horizontal rack PDU G4 - Basic PDU G4 UPDU (EHBAGU15A) | 415 | 55 | n/p | ? phase? | ↗ | |
| Eaton | horizontal rack PDU G4 - Basic PDU G4 UPDU (EHBAGU15Q) | 415 | 55 | n/p | ? phase? | ↗ | |
| Eaton | horizontal rack PDU G4 - Managed PDU G4 UPDU (EHMAGU23A) | 415 | 55 | n/p | ? phase? | ↗ | |
| Eaton | horizontal rack PDU G4 - Managed PDU G4 UPDU (EHMAGU23D) | 415 | 55 | n/p | ? phase? | ↗ | |
| Eaton | horizontal rack PDU G4 - Metered-input PDU G4 UPDU (EHMIGU23A) | 415 | 55 | n/p | ? phase? | ↗ | |
| Eaton | horizontal rack PDU G4 - Metered-input PDU G4 UPDU (EHMIGU23D) | 415 | 55 | n/p | ? phase? | ↗ | |
| Eaton | Managed Rack PDU G4 (Remote management with outlet-level monitor ×3 identical | 415 | 63 | n/p | ? phase? | ↗ | |
| Eaton | Metered Input Rack PDU G4 (Remote management with bank-level mon ×3 identical | 415 | 63 | n/p | ? phase? | ↗ |
4 carrying feeds × 57.6 kW printed maximum input; the OCPD must be rated at 125% of the continuous load, so 46.1 kW each. Power factor assumed 1.0. The vendor prints this ceiling, so it is used in place of V × A × √3.